CONNECTING THE VALVE WIRING
1. To provide a field common wire, attach one wire to either solenoid
lead of all sprinkler valves and master valve (optional).
2. Attach a separate control wire to the remaining solenoid lead of
each valve. Label the control wires with the intended station
number for identification at the controller.
Caution: All wiring splices must be waterproofed to prevent
short circuits and corrosion.
A maximum load of 12 VA (0.5 amps) may be connected to
each station. A maximum load (including master valve) of
30 VA (1.25 amps) may be programmed to operate
simultaneously. Exceeding these limits can damage the
controller.
3. Route the control and common wires into the controller cabinet
through the 2" (52mm) access opening. Remove approximately
1/2" (13mm) insulation from the ends of each wire.
4. Attach the field common wire to one of the three valve common
terminals labeled
VC/COM.
5. Referring to
Figure 4, connect each valve control wire to the
appropriate station number terminal. If an optional master valve
is installed, connect its control wire to the terminal labeled
MV/PUMP. Tighten all terminal screws securely.
Installation Procedures
Pump Start
Relay
or
Master Valve
Valve Common
Figure 4
Valve Station 1
Valve Station 2
Valve Station 3